Ultra-Aire 135H Whole House Ventilating DehumidifierUA-135H • Part No. 4025470 • Serial No.________________________________INSTALLER’S & OWNER’S MA
10ATTENTION INSTALLERWIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOWWARNING: DO NOT allow the yellow lead from the unit to contact the
FOR HVAC INSTALLER ONLY5. (DEH 2000) DIGITAL CONTROL Installation Instructions 5.1 Specifications Model: 4024539 Electrical: 24 VAC Humidity Range:
WARNING Warning: Connecting the white wire to the control terminal without use of a motorized damper could create a short resulting in damage to the t
135.3E Setting Relative Humidity Set point The relative humidity Set point operates the dehumidifier function of the Ultra-Aire. It has no effect on an
5.3I Intermittent or Programmed Ventilation With the damper in program mode (denoted by “Pr” when setting the damper operation) the system will operat
15FOR HVAC INSTALLER AND HOMEOWNER6. ServiceCAUTION: Servicing the UA-135H with its high pressure refrigerant system and high voltage circuitry presen
16only the impeller fan should run. Disconnect the wires.3. Connect the yellow and blue pigtails from the main unit together; the compressor and impe
WIRING DIAGRAMS17UA-135H With Humidity/Fan Control (4024155) UA-135H W/Ventilation Timer/Humidity/Fan Control (4024125)UA-135H With DEH 2000 Digital C
OPTIONAL PARTS LIST18Ultra-Aire 135H Installer’s & Owner’s ManualItem Part No. Description 1 4024125 Control Panel Assembly, Ventilation
SERVICE PARTS LIST19Ultra-Aire 135H Installer’s & Owner’s ManualItem Part No. Description 1 4021589 Capillary Tube, .059" X .124&quo
Table of ContentsSafety Precautions ...31.Intended Application ...
20Ultra-Aire 135H Installer’s & Owner’s ManualWARRANTOR: Therma-Stor LLCPO Box 8680Madison, WI 53708Telephone: 1-800-533-7533.WARRANTY: This warra
Ultra-Aire 135H Installer’s & Owner’s ManualPO Box 8680 • Madison, WI 53708 Phone: 608-222-5301 • Fax: 608-222-1447 Web: www.thermastor.com • Emai
Safety PrecautionsRead the installation, operation and maintenance instructions carefully before installing and operating this device. Proper adherenc
1. Intended Application for Ultra-Aire 135HFor the ideal installation, draw air from the central part of the home and return it to the isolated areas
4.3 Electrical RequirementsWARNING: Do not allow the yellow lead from the Ultra-Aire to contact the red lead or orange lead from the Ultra-Aire or dam
Duct Sizing: For total duct lengths up to 25', use a minimum 10" diameter round or equivalent rectangular. For longer lengths, use a minimum
Ultra-Aire return. Always select a return from a central location in the structure in an area that is always open to the rest of the structure. Do not
4.7A Humidity/Fan Control Panel WITHOUT Fresh Air Ventilation or DamperThe humidity/fan control panel automatically controls the humidity of the livi
9panel receives 24Vac from the UA-135H. If 24Vac is present at the control panel, reset the timer by pressing the reset button at the bottom center of